30KW to 56KW Perkins range Diesel Generator sets/generating set
MAIN SPECFICATIONS OF GENSETS |
GENSET |
Continuous Model |
P30 |
P34 |
P36 |
P40 |
P45 |
P56 |
Continuous Output |
30/38 |
34/42 |
36/45 |
40/50 |
45/60 |
56/70 |
TECHNICAL DATA |
DIESEL ENGINE MODEL |
1004G |
1004G |
1004G |
1004TG |
1004TG |
1004TG |
Engine Characters |
Water-cooled, in line, 4-cylinders, 4stroke, direct injection,Dry cylinder liner, 1500rpm |
Constant Output(KW) |
40 |
65.7 |
Standby Output(KW) |
44 |
72.3 |
Aspiration |
natural |
Turbochargered |
Bore(mm)xStroke(mm) |
100x127 |
Cubic Capacity(liters) |
3.99 |
3.99 |
Piston Speed(m/s) |
6.35 |
6.35 |
Compression Ratio |
16.0:1 |
16.0:1 |
Stability bandwidth |
≤±0.8% |
Steady governing rate |
≤5% |
≤5% |
Acoustic Pressure |
≤91.2dBA(at full load,1m distance) |
≤91.2dBA(at full load,1m distance) |
Exhaust temperature(℃) |
600 |
600 |
Exhaust Back pressure |
5KPa |
6KPa |
Air Induction System |
Dry element type with back pressure warning indication |
Lube Temperature/capacity |
125℃/8.1L(MAX) |
BMEP:Kpa(prime power) |
882 |
1369 |
Heat Rejection to Exhaust |
35.7KW/min |
53.4KW/min |
Heat Rejection to Cooling |
38KW/min |
43KW/min |
Cooling System Volume |
21L |
22.2L |
Cooling Air Flow |
55m3/min |
100m3/min |
Combustion Air Flow |
2.64m3/min |
4.52m3/min |
Exhaust Gas Flow |
7.54m3/min |
13.1m3/min |
Min. Fuel Consumption |
≤210g/kw.h |
≤205g/kw.h |
ALTERNATOR MODEL |
YHG184H |
YHG224C |
YHG224D |
YHG224D |
YHG224E |
YHG224F |
Continuous Output(KW/KVA) |
30/37.5 |
34/42.5 |
40/50 |
40/50 |
48/60 |
58/72.5 |
Power Efficiency |
86.3% |
87% |
88.2% |
88.2% |
88.6% |
90% |
Voltage Regulation |
±1.0% with 4% engine governing |
Waveform Distortion |
No load<1.5%, and non-distorting balanced linear load<5% |
THF/TIF |
<2%/<50 |